Learn first: Electromagnetic induction
The current in a wall socket is alternating: its size and direction go through 50 complete cycles every second. Such current is easy to generate, to step up or down with a transformer and to send over long distances. In this topic we study rms values, inductive and capacitive reactance, the RLC circuit, resonance, the power factor and the transformer.
A coil of N turns and area S rotates with angular velocity ω in a uniform field B. The flux Φ = BS·cos ωt changes, and by the law of electromagnetic induction an EMF appears:
e = E_max·sin ωt, E_max = NBSω
A 100-turn coil of area 200 cm² rotates at 50 Hz in a 0.1 T field. Peak EMF?
The effective value of an alternating current is the direct current that would release the same heat in a resistor:
I = I_max/√2, U = U_max/√2
Ammeters, voltmeters and device labels show rms values. For "220 V" mains the peak is U_max = 220·√2 ≈ 311 V.
Reading an equation: from u = 311·sin 314t we get U_max = 311 V, U = 220 V, ω = 314 rad/s, ν = ω/(2π) = 50 Hz.
X_L = ωL
X_C = 1/(ωC)
As frequency rises, X_L increases and X_C decreases.
Find the reactances of a coil L = 0.1 H and a capacitor C = 100 μF at 50 Hz.
The voltages across the elements are out of phase, so the resistances add like vectors, not like ordinary numbers:
Impedance: Z = √(R² + (X_L − X_C)²)
Ohm’s law: I = U/Z
Phase shift: cos φ = R/Z
Resonance occurs when X_L = X_C: Z = R is smallest and the current is greatest.
ω₀ = 1/√(LC), ν₀ = 1/(2π√(LC))
This equals the natural frequency of the LC circuit.
R = 8 Ω, X_C = 9 Ω, X_L = 3 Ω, U = 140 V. Current and power?
Energy is used up only in the resistance; the coil and capacitor take energy during part of a cycle and give it back.
Active (real) power: P = UI·cos φ = I²R
cos φ is the power factor. If it is small, a larger current is needed for the same power and line losses grow, so factories try to raise cos φ.
A transformer is two windings on a common steel core. Alternating current in the primary creates a changing flux in the core, which induces an EMF in the secondary. A transformer does not work on direct current.
U₁/U₂ = N₁/N₂ = k, for an ideal transformer U₁I₁ = U₂I₂
N₁ = 1000, N₂ = 50, U₁ = 220 V. The secondary current is 2 A. Find U₂ and I₁.
Power-station generators have not one but three windings, turned 120° relative to one another. So the three emfs have the same amplitude and frequency but are shifted in phase by 120° (a third of a period). This is the three-phase system. Four wires reach the consumer: three phase (live) wires and one neutral.
Phase voltage (phase–neutral): U_ph = 220 V; line voltage (phase–phase): U_l = √3·U_ph ≈ 380 V
Homes are usually supplied with one phase and neutral (220 V), industrial motors with all three phases (380 V). The advantages of three-phase supply: more power is carried with fewer wires, with balanced loads the neutral current is almost zero, and three-phase current produces a rotating magnetic field in a motor — which is why induction motors are simple and reliable.
When power is transmitted through line wires of resistance R_l, the loss in them is ΔP = I²R_l. Since the power transmitted is P = UI (with cos φ = 1):
ΔP = P²R_l/U²
Raising the voltage n times cuts the loss by n². That is why at the power station a transformer raises the voltage to hundreds of kilovolts, and near the town it is stepped down in stages to 10 kV and then to 380/220 V.
What is the line voltage of a supply with a phase voltage of 220 V?
100 kW is transmitted along a line of resistance 0.5 Ω (cos φ = 1). Losses at 10 kV and at 400 V?